Real-time air monitoring report, PS 234M, Dec 2001

Machine-extracted title · confidence 95%

Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.

NYC-WTC_000177887–000177891
Page image
Scanned page image, NYC-WTC_000177890
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan Januaiy' 11, 2002 Real-Time Air Monitoring Page 4 P.S. 234 (Manhattan) ATCPrpiectNpJ5O912S:0279

Only one indoor reading, recorded in Room 315 on the afternoon of December 8^^, exceeded the value of the EPA ambient-air quality standard of 65 ug/m^. It bears repeating that the standard is a 24-hour average and the measured level is an instantaneous reading. All other indoor readings were below 65 ug/m^.

Nitrogen Dioxide CNQ-)) Table 3 summarizes the NO2 data for each day. As with the particulate data displayed above, the indoor levels were consistent with outdoor levels.

TABLES NO2 LEVELS PARTS PER MILLION (ppm) . A TA.. , . ' D ATE :}LQCATIGN;' AVERAGE HIGH LOW <5'» ■■■ J It W It"" ; ■'A

Indoors 02 0.6 0^0 Dec. 8 Outdoors 0.2 0.6 0.0

Indoors 0.1 0.4 0.0 Dec. 9 Outdoors 0.2 0.6 0.0

Indoors 0.2 0.6 0.1 Dec. 10 Outdoors 0.3 0.6 0.0

Indoors 0.3 0.6 0.0 Dec. 12 Outdoors 0.4 0.7 0.1

Eleven of forty-four indoor readings were 0.0 ppm, all other indoor readings were 0.1 - 0.6 ppm. The EPA ambient-air quality standard of 0.053 ppm is an annual average. The same is true of the New York State standard of 0.05 ppm (100 ug/m^). The measurements summanzed in the table are instantaneous readings. A direct correlation between these readings and the standards cannot be made.

Other Parameters

NO, SO2, H2S and TVOC were not detected on any of the four days.

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Measurements of concentrations of temperature, relative humidity, CO2 and CO were within recommended guideline ranges (building unoccupied);

CONFIDENTIAL, CITY_21MC100_003444798 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000177890

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000177890Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, PS 234M, Jan 2002

NYC-WTC_000177847

Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.

Similar indexed content

Compare copies and versions →