NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan August 28, 2002
Indoor Air Quality Assessment Page 2
P.S. 130 M ATC Project No. 15-19125-0345
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times. The information presented in this report should be
used by the DOE as a guide to assess the need for further improvements in current indoor air
quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999f American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLE 1
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
lARGET
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)____________ above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
ICO)__________ USEPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2.5) of air 24-hour average
40 pg/m^ 24-hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer: VS-TO^F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_2IMCl00_003430727
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000175232