A. Ceiling:
1) .\ 30 pieces counted as damaged or discolored due to workmanship from
various contractors. Mazen Batarseh from Ambassador Const. Co. Inc.
advised an attempt was made to clean tiles, but cleaning was unsuccessful.
B. Walls:
1) Spackle / paint structural cross members meet walls
2) Spackle / paint column with recessed fire extinguisher ( comer bead }
C. Flooring:
1) No problems found
D. Electrical:
1) Roll down window shades are electrically operated (low voltage) no
installation of any wiring to operate shades.
Juan Mejia made note and will discuss with Ambassador on how to
resolve. I will follow up.
2) Cable wire coming out of electrical box under recessed fi re extinguisher
wall, needs cable box cover. Question - which vender is responsible?
3) Phone wire is coming out from behind heating going over support column
and under wall ? Needs to be relocated. Unknown what this wire is for.
E. Mise:
1) Electric roll down shades, spec’s called for dual shades,
If
1 st being solar shades,
2 nd being a black out shade (room darkener)
At present there is a single roll shade in place at all window locations, but
no wiring and switching.
Question for Juan Mejia: Were these shades to be controlled by the touch
pad screen through the A / V system ? I will follow up.