NYC 9/11 Public Portal Document
•SC.v’ OTHER regulatory INEORMATlON-.(Cont>nued)
U S- DOT (Continued)
N^te; Yuasa-Exide batteries which have met the test requirements for ’nori’Spiiiable wet electric Storage batteries’,
as provided m 49 CFR 173.159(di, are non-repulated by DOT when protected against short circuits and securely
packaged. Contact your Yuasa-Exide reprssentative to determine which non-spiiiable batteries have met these
requirements.
If non-spillable wet electric storape batteries have, [rot met these requirements, the foliowino information would
apply:
Proper Shipping Name: Batteries, wet, nen-spiiiable
Hazard Class/Division; 8
ID Number; UN2800
Packinc Group; 111
Label Required: Corrosive
SCRA/ Spent lead-acid batteries are not resulated a$ hazardous waste when recycled. Spilled sulfuric acid is s
characteristic hazardous waste; £PA hazardous waste number £002 (corrosivity).
CERCLA (Superfundl and FPCRA:
|3) Reportable Quantity (RQ) fprspiileiJ 100% sulfuric acid under CERCLA (Superfund) and EPCRA (Emereency
Ptanninp and Community Riphtto Know Act) Is 1 .OOP lb$. State and loc:al reportable quantities for spilled
sulfuric acid may vary.
<b) Sulfuric acid is a listed 'Extremely Hazardous Substance’ under EPCRA, with a Threshold Planning Quantity
(TPQ) of 1.000 -lbs.
(cj ERCRA Section 302 notification i$ required if 1,000 lbs. or more Of sulfuric acid is present at one site. The
quantity Pf sulfuric acid will vary by battery type. Contact your Yuasa-Exide representative for edditional
inforntatioh,
Wl EPCRA Section 312 Tier 2 reportinfl is required for batteries if sulfuric acid is present in quantities of 500
tbs. or more and/or if lead is present in quantities of 10,000 lbs or more.
Ie) Supplier Notification: This product contains toxic chemicals which may be reportable under EPCRA Section
313 Toxic Chemical Release Inventory (Form R) requirements. If you are a manufacturing facility untier SIC
codes 20 through 39, the following information is provided to enable you to complete the required reports;
•
Approximate
Toxic Chemical CAS..Nun>ber % hv Weioht
Lead 7439-921 60
SuKufic Acid 7664-93-9 10-30
• Antimony 7440’36-0 2
Arsenic 7440-38'2 0.2
If you distribute this product to other manufacturers in SIC Codes 20 thfouph 39, this Information must be
provided with the first shipment of each calendar year.
The Section St3 supplier notification requirement does not apply to batteries which are *00050:1161
products’.
• Not present in all battery types. Contsct your Vuasa-Exide representative tor additional information.