NYC 9/11 Public Portal Document
FIRE DEPARTMENT
250 LIVINGSTON STREET BROOKLYN, N.Y. 11201-5884
BUREAU OF FIRE PREVENTION
RANGEHOOD CHECKLIST
DATE:
FOLDER #
PREMISES: 3^ Dept. AltT^se.
F.D. Plan #
Name of Contractor:.___ .
TO WHOM IT MAY CONCERN:
J ^101 is Voft.
Plans submitted to this office have been examined and found to be acceptfor an inspection and
test at this time; The plan will be re-examined ^er the following defects
are corrected:
ey. ■
□ 1. An original approved Building Dept, plan and application/amendment have not been submitted.
□ 2. Brand name, model number and B.S. & A. approval number of system not indicated.
□ 3. A Building Dept, approved plot plan to scale showing the location of the extinguishing system in relation
to the balance of the building not submitted.
□ 4. Hood and Duct size has not been indicated.
□ 5. Pipe size has not been indicated.
•□ 6. The number and size of extinguishing agent containers has not been indicated.
□ 7. The type of extinguishing agent has not been indicated.
□ 8. The number of surface, plenum and duct nozzles have not been indicated and do not meet manufacturers
specifications.
□ 9. The number of fusible links and temperature setting has not been indicated.
□ 10. Location and distance of remote manual pull station not shown (10—35' from hood required).
□ 11. An automatic gas or electric shut-off valve not indicated.
n 12. Approved B.S. & A. grease filters statement not included. NOTE: Actual approval number is not necessary.
□ 13. Name of B.S.,& A. approved (Secowash, Quest Clear, Air, Cyclowash or Gaylord) Grease Extractor System
approval No. not included.
n 14. Damper requirements as per RS-13-3 as modified by the Board of Standards and Appeals under Cal. #695-84
B.C.R. Sections 3-2.9.4 have not been met.
□ 15. The exhaust fan operation upon discharge does not conform to RS-13,-7-2.4.
n 16. Type and location of cooking appliances have not been indicated.
□ 17. Surface dimensions (length & width) of ail appliances.
□ 18. System not installed as per manufacturers specifications.
□ 19. Model No. of nozzles omitted/incorrect.
□ 20. Clearance between open flame and deep fat fryers has not been indicated. (16" space or vertical baffle).
□ 21. Duct statement has not been indicated. (Additional ducts have been tied in and meet the requirements of
RS-13-3 as shown on drawing, —or— no other ducts are tied into the fire system hood).
□ 22. Other: ___________________________________________________________________________
Xy CHl^OF FIRE PREVE^ON
-TW4-2-117