floor ceiling by the Liberty Street entrance is made of gypsum board. The ceiling on the Cedar
Street entrance consists of suspended acoustical tile covered with decorative tin facing. Above
the suspended ceiling is a two-foot void space that houses the HVAC system for the
establishment. The basement ceiling is a suspended fibrous tile ceiling. The void space above
both suspended ceilings and the gypsum ceiling contained both WTC-related and non-WTC-
related dust. Asbestos pipe insulation was present in the void space of the basement. Grills,
refrigerators, tables and chairs were present on the first floor. The basement contains walk-in
refrigerators, preparation tables, stoves, dishwashing areas and dry goods storage. Prior to
cleaning, all open and bulk stored food, fibrous ceiling tiles in the basement, and wrap insulation
that had surrounded the HVAC systems were disposed.
Cleaning Method - This unit was cleaned using Test 4A and Test 4D. Test 4A consisted of use
of an industrial HEPA-filtered vacuum and an AFD. All horizontal surfaces were wet wiped.
Test 4D consisted of cleaning of the HVAC system by a subcontractor utilizing standard industry
cleaning techniques.
Cleaning Results - This unit met the clearance criteria listed in Table 1.0 for each compound after
being cleaned once.
Asbestos
Before Cleaning Samples - One wipe sample and one bulk sample were collected from
the HVAC system. The wipe sample concentration was below the detection limit,
however the detection limit was much higher than the other wipe sample detection limit
(approximately 300,000 vs. 3,000). The bulk sample was analyzed by PLM and asbestos
was not detected.
Post P* Cleaning Samples (Test 4A) - Eight air samples were collected for asbestos. The
air samples were analyzed for PCM, TEM AHERA, and PCMe. The PCM results indicate
that six of the samples were below the detection limit and all eight samples were below the
secondary numeric criterion of 0.01 ftcc. The TEM AHERA results indicate that seven of
the samples were below the detection limit and all eight samples were below the numeric
criterion of0.022 S/cc. The PCMe results indicate that all eight of the air samples were
below the detection limit and below the primary clearance criterion of0.0009 S/cc.
Post P‘ Cleaning, HVAC System - Three air and two wipe samples were collected. The
air samples were analyzed for PCM, TEM AHERA, and PCMe. The PCM results indicate
that all of the samples were below the secondary numeric criterion of 0.01 free. The TEM
AHERA results indicate that two of the samples were below the detection limit and the
third was at the detection limit with all three being below the secondary numeric criterion
of0.022 S/cc. The PCMe results indicate that two of the samples were below the
detection limit and the third was at the detection limit with all three being below the
primary clearance criterion of 0.0009 S/cc.
Gypsum
Before Cleaning Samples - Pre-cleaning air samples were not collected.
Post Cleaning Samples, HVAC System - One air sample was collected after the first