NYC 9/11 Public Portal Document
exposure, uncertainty, and technical limitations, that may justify a cleanup remedy
that departs from the 1-in-l,000,000 cleanup goal.
In contrast to the above criteria, EPA’s Lower Manhattan indoor cleanup
established a 1-in-l0,000 risk as the goal of the cleanup for asbestos. The
program does not include monitoring for the presence of the other COPCs.
including dioxin and PAHs, which are known carcinogens. The COPC document
established benchmarks for these two pollutants that also correspond to a 1-in-
10,000 increased risk. Although the assumption is that the cleaning methods
prescribed for asbestos will clean the residence of other pollutants as well, the
post-cleaning testing does not provide assurance that these other pollutants were
removed. However, under Superfund guidance, the risk from exposure to
multiple carcinogens is considered additive. Thus, if all three pollutants were
cleaned up to levels that equate to a 1-in-l0,000 risk for each pollutant, the
s?>*' combined risk would be considered greater than 1-in-l0,000.
The TERA peer review addressed the risk level established for the COPCs. The
panel suggested that the document more clearly explain how the impact of being
exposed to mixtures of the COPCs was considered in developing the benchmarks.
Further, panel members disagreed with the rationale for using an upper level
excess lifetime cancer risk of l-in-lO.OOO. The workgroup’s response to the peer
review panel stated the risk level was appropriate because of practical sampling
limitations for asbestos, noting a sampling time of 800 hours would be required to
achieve the air monitoring results needed to support a 1-in-1,000,000 increased
lifetime risk level. The workgroup acknowledged that running multiple pumps
concurrently could reduce total sample time, but did not judge this practical since
more than 6,000 individual residences signed up for the cleaning program.
Need to Treat Impacted Buildings as a System
. ^eS**^* Tests of indoor asbestos contamination have shown that the distribution of
asbestos within indoor spaces is not consistent. Selective cleaning of apartments
does not ensure that uncleaned residences or imcleaned objects in apartments are
free of asbestos contamination. In the case of centralized HVAC systems,
selective cleaning does not ensure that cleaned apartments will not be
re-contaminated by uncleaned apartments through the HVAC system.
Consequently, the cleaning of contaminated buildings should proceed by treating
the building as a system.
A 1\ systematic approach to cleaning would require that the exterior of the
W building be cleaned first before the building is re-occupied. All possible entrances
0 / tv outside air should be sealed off and the building HVAC shut down during I
exterior cleaning. Once the exterior is cleaned, interior cleaning can begin. For 1/ I
Hf A V buildings with centralized air and heating, the interior surfaces of supply ducts sadl/^C(^
“A \ return air plenums, fan housings, and filter housings should be cleaned. Filters
0^\ should be removed, filter tracks cleaned, and new filters installed. The above
51
'ket*- .,v'' ,
reSu |4« £
NYC-WTC_000145691
OCR can misread numbers and units. Confirm readings against the page image before using them.