NYC 9/11 Public Portal Document
Attn: CTSI-Consulting & Testing Services, Inc. Customer ID: CTS150
622 Georges Rd. Customer PO:
North Brunswick, NJ 08902
Received: 09/27/01 3:30 PM
Fax: (732) 729-1803 Phone: 732-729-1800
EMSL Order. 030104997
Project: 115 Broadway I Entire Bldg EMSL Project ID:
Analysis Date: 9/2712001
Fiber Analysis of Air Samples via NIOSH 7400, Revision 3, Issue 2, 8/15194
LOD Fibers/ Fibers/
Sample Location Sample Date Volume Fibers Fields (Jib/cc) mm2 cc Notes
01 19 Fl West side 9/27/2001 2025.00 12.0 100 0.001 15.29 0.003
030104997-0001
02 19 FI Center 9/27/2001 2025.00 14.0 100 0.001 17.83 0.003
030104997-0002
03 19 FI East side 9/27/2001 2025.00 12.0 100 0.001 15.29 0.003
030104997-0003
04 18 Fl West side 9/27/2001 1800.00 15.0 100 0,001 19.11 0.004
030104997-0004
05 18 FI Center 9/27/2001 1800.00 12.5 100 0.001 15.92 0.003
030104997-0005
06 18 FI East Side 9/27/2001 1800.00 23.0 100 0.001 29.3 0.006
030104997-0006
07 17 FI West Side 9/27/2001 1860.00 25.0 100 0.001 31.85 0.007
030104997-0007
08 17 Fl Center 9/27/2001 1860.00 16.0 100 0.001 20.38 0.004
030104997-0008
09 17 F1 East Side 9/27/2001 1860.00 26.0 100 0.001 33.12 0.007
030104997-0009
10 16 FI West Side 9/27/2001 1950.00 19.0 100 0.001 24.2 0.005
030104997-0010
11 16 FI Center 9/27/2001 1950.00 24.0 100 0.001 30.57 0.006
030104997-0011
12 16 FI East Side 9/27/2001 1950.00 22.5 100 0.001 28.66 0.006
030104997-0012
Thomas Michel
Analyst Laboratory Manager
or other approved signatory
~rteo to noerucc, wnrcn is aepencant on vowme
relates only to the emnples reported above. This report may not be except in full, without written approval by EMSL
Analysis performed by EMSL Manhattan (NY State ELAP #11606)
I
NYC-WTC 000133063
OCR can misread numbers and units. Confirm readings against the page image before using them.