November 23, 2001
Mr. Kevin Hoey
Property Manager
CAPITAL PROPERTIES
111 Broadway
New York, NY 10006
RE: ENVIRONMENTAL SAMPLING SERVICES PERFORMED AT
111 BROADWAY, ENTIRE BUILDING, NEW YORK, NY
Dear Mr. Hoey:
On November 21s`, 2001, Consulting and Testing Services, Inc. (CTSI) has performed air
quality sampling from various floors from the above referenced building.
Air samples were collected as part of building air quality/dust control evaluation from all the
floors and Trinity level (east). All samples collected were transported to an independent certified
laboratory, EMSL Analytical, for analysis. Samples were analyzed utilizing Phase Contrast
Microscopy (PCM) Methodology (Fiber Analysis of Air Samples via NIOSH 7400, Revision 3,
Issue 2, 8/15/94).
Based on the attached certificate of analysis, the air quality samples collected on November 21",
2001, indicate fiber counts are within the Occupational Safety & Health Administration
(OSHA) Permissible Exposure Limit (PEL) of 0.1 f/cc (fibers per cubic centimeter). A total of
twenty four (24) air quality samples were collected.
Please feel free to call us with any questions or if you need further information.
Sincerely,
CONSULTING AND TESTING SERVICES, INC.
~le;~~"
Frank Salami
President
'CC: David Parisier
Attach.