AKRF,Inc. 111-115 Broadway,New York, New York
1.0 INTRODUCTION
AKRF, Inc. (AKRF) was retained by Rosenman & Colin LLP to perform Indoor Air Monitoring
within 111-115 Broadway in New York City. The project site consists of two (2) twenty-one
story buildings; 115 Broadway is located north of 111 Broadway, and Thames Street runs
between the two buildings. The buildings are approximately 98 years old and are mirror images
of each other.
Two Heating, Ventilation and Air Conditioning (HVAC) rooms are located on each of the floors.
The HVAC rooms are located on the south side of 115 Broadway and on the north side of 111
Broadway, both overlooking Thames Street. It is our understanding that the grills that allow the
flow of fresh air into the HVAC rooms have been closed since the destruction of the World
Trade Center on September 11, 2001. The windows are original to the buildings and are
operable, but do not provide an airtight seal. It has been expected that outside air and particles
could enter the buildings through closed windows. Various floors have installed new (and
presumably air-tight) windows within the original windows.
AKRF collected air samples for laboratory analysis at sixteen locations throughout the project
site between November 26 and 30, 2001. The air samples were analyzed for the following
constituents: Volatile Organic Compounds (VOCs), Polycyclic Aromatic Hydrocarbons (PAHs),
metals, Aldehydes, asbestos fibers, silica, respirable particulates and dioxins. In addition,
temperature, Relative Humidity, Carbon Dioxide and Carbon Monoxide concentrations were
measured throughout the buildings using a Metrosonics aq-5000 direct read meter. The observed
concentrations were compared to established occupational exposure values required by the
United States Department of Labor, Occupational Health and Safety Administration (OSHA).
OSHA has established permissible exposure levels (PELs); the values that an employer may
expose an employee to for a normal eight-hour workday, 40-hour workweek, 50-week workyear,
over a normal work lifetime. Other occupational exposure values are the National Institute for
Occupational Safety and Health (NIOSH) recommended exposure levels (RELs) and the
American Council of Governmental Industrial Hygienists (ACGIH) threshold limit values
(TLVs). Both the RELs and TLVs are intended to cover similar environments as the PELs. The
American Society for Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) has
developed guidelines and recommendations for providing acceptable indoor air quality. The
ASHRAE guidelines are provided within various Standards providing for acceptable
environmental conditions and ventilation.
2.0 TECHNICAL OVERVIEW
The following is a general profile of the air monitoring execution and results.
2.1 Polycyclic Aromatic Hydrocarbons
Polycyclic aromatic hydrocarbons (PAHs) are a class of compounds formed during incomplete
combustion of oil, coal, gas, garbage and other organic substances. PAHs are found in
petroleum and related products and are manufactured for use in dyes, insecticides, solvents and
asphalt. PAHs were sampled and analyzed in accordance with NIOSH Method 5506. The
sampling method requires air to be drawn through a 2 micrometer (µm) Teflon membrane filter
and an XAD-2 sorbent tube containing collection resin utilizing a personal sampling pump. The
sampling pump was calibrated, utilizing a rotometer, with a representative sampler in line prior
to and after each sample collection. Immediately after sampling, the membrane filter was
transferred to a culture tube and the sorbent tube was capped. The culture tube and sorbent tube