NYC 9/11 Public Portal Document
JLC ENVIRONMENTAL CONSULTANTS, INC.
200 Park Avenue South, Suite 1001, New York, New York 10003
Phone: (212)420-8119 Fax:(212)420-6092
Project No.: 01-2089004
Rose Associates Inc. ELAP Lab Code: 11029 Analyte: FIBERS
200 Madison Ave. 5th Floor NIOSH and AIHA Lab Code: 100273 Date Received: 10/25/2001
New York, NY 10016 NVLAP Lab Code: 101953 Date Analyzed: 10/25/2001
Batch #: 0110A824
SUMMARY OF ANALYTICAL RESULTS
Site: 21 West Street, New York, NY
SAMPLE #
COLLECTED DESCRIPTION / LOCATION TIME(min) VOLUME(I) FIB/FIELD RESULTS(f/cc)
LAB #
013 Ambient/ 11th Floor/ Apt. 11Cl At the North 120 1846 61100 0.002
24-October Section of the Living Room
A 8316
014 Ambient/ 11th Floor/ Hallway Between Apt. 11H 120 1846 4/100 0.001<LOD
24-October and 11J
A 8317
015 Ambient/ 9th Floor/ Apt. 9N/ At the North Section 120 1846 3/100 <0.001<LOD
24-October of the Living Room
A 8318
016 Ambient/ 9th Floor/ Hallway Between Apt. 9H and 120 1846 4/100 0.001<LOD
24-October 9J
A 8319
017 Ambient/ 8th Floor/ Apt. 8E/ At the North Section 120 1846 3/100 <0.001<LOD
24-October of the Living Room
A 8320
018 Ambient/ 8th Floor/ Hallway Between Apt. 8H and 120 1846 4/100 0.001<LOD
24-October 8J
A 8321
Sample Analysis by: <LOD = Less than limit of detection which Is 5.5 Fibers/ 100 Fields
VOIDI = H.C.P. ( High Concentration of Particles)
Positive Phase Contrast Microscopy (PCM) VOID2 = Overloaded
Method of Samcla Preparation and Analysis:
All samples analyzed in accordance with the NIOSH 7400 Method using "A" Counting Rules. Issue 2, August 1994
Instrumentation:
Gulam aCr11
Olympus PCM Model BI-I-2 with Walton-Beckett Graticule (100um field diameter).
Laboratory Director
Report Date: November 8, 2001
JLC Is responsible for only the fiber counts within the limitations of the method described as NIOSH 7400. Among other limitations, this metho
gives only an index of airborne fibers and provides only an estimate of asbestos concentration. Any and all claims arising out of JLC's analyst:
these samples are limited In recovery to the cost of analyzing samples. JLC accepts no other liability and the client agrees to seek no costs bi
the above.
Page 3 of 5
NYC-WTC 000094652
OCR can misread numbers and units. Confirm readings against the page image before using them.