Method 200.8 ICP-MS lab results, NEWE samples, Jan 11, 2002
Machine-extracted title · confidence 85%
ICP-MS analysis of water samples using Method 200.8 with elemental measurements (Be, Sc, Mn, In, Sb, Ho) and quality control replicates performed on January 11, 2002.
Concentration Results
Analyte Mass Meas. Intens. Mean Meas. Intens. RSD Net Intens. Mean Cone. Mean Cone. RSD Sample Unit
r Be 9 14571.486 2.488 0.024 30.16189 3.13 ug/L
|> Sc-1 45 610570.746 1.842 610570.746 ug/L
L Mn 55 515866.105 2.877 0.844 29.26006 2.95 ug/L
r> In 115 1250930.307 1.164 1250930.307 ug/L
I Sb 121 240288.062 0.911 0.192 29.80908 1.90 ug/L
L Sb 123 186575.146 0.871 0.149 30.15966 1.27 ug/L
r> Ho 165 1707289.635 2.036 1707289.635 ug/L
L Tl 205 798910.931 1.262 0.468 30.24462 1.05 ug/L
QC Calculated Values
Analyte Mass QC Std % Recovery Int Std % Recovery Spike % Recovery Dilution % Diff Dup. Rei. % Diff
r Be 9
1> Sc-1 45 96.161
L Mn 55
r> In 115 94.855
I Sb 121
L Sb 123
r> Ho 165 95.059
L Tl 205
Calibration
Analyte MassCurve Type Correlation Coefficient
r Be 9Linear Thru Zero 0.999992
|> Sc-1 45Linear Thru Zero
L Mn 55Linear Thru Zero 0.999983
r> In HSLinear Thru Zero
I Sb 121 Linear Thru Zero 0.999998
L Sb 123Linear Thru Zero 1.000000
r> Ho 165 Linear Thru Zero
L Tl 205Linear Thru Zero 0.999977