NYC 9/11 Public Portal Document Quantitation Report (Not Reviewed)

Data File C:\HPCHEM\l\DATA\02apr03\7498D.D Vial: 7 Acq On 3 Apr 2002 1:43 pm Operator: 201-wb Sample nyc; dup Inst : GC/MS Ins Mise Multiplr: 1.00 MS Integration Params: RTEINT.P Quant Time: Apr 3 14:21 2002 Quant Results File: HP031802.RES

Quant Method : C:\HPCHEM\1\METHODS\HP031802.M (RTE Integrator) Title : VOCs BY EPA METHOD 524 Last Update : Thu Mar 28 15:03:13 2002 Response via : Initial Calibration DataAcq Meth : HP031802

Internal Standards R.T. Qlon Response Cone Units Dev(Min)

1) 1,4-DIFLUOROBENZENE 15.14 114 801283 5.00 ug/L 0.09 24) CHLOROBENZENE-D5 21.79 117 650769 5.00 ug/L 0.09 52) 1,4-DICHLOROBENZENE-D4 26.99 152 279074 5.00 ug/L 0.10

System Monitoring Compounds 2) 1,2-DICHLOROETHANE-D4 14.37 65 354578 5.37 ug/L 0.09 Spiked Amount 5.000 Recovery = 107.40% 3) 4-BROMOFLUOROBENZENE 24.38 174 227528 3.51 ug/L 0.09 Spiked Amount 5.000 Recovery = 70.20% 25) TOLUENE-D8 18.49 98 903793 5.73 ug/L 0.09 Spiked Amount 5.000 Recovery = 114.60%

Target Compounds Qvalue 12) ACETONE 8.29 43 11765- 2.73 ug/L 92 21) CHLOROFORM 12.86 83 9122 0.15 ug/L 98

(#) = qualifier out of range (m) = manual integration 7498D.D HP031802.M Wed Apr 03 14:21:35 2002 Page 1

NYC-WTC_000081588

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000081588Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →