REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample HILLVIEW
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 3
Dr. Ian Hurley ID of Source:
Received LK Collection 10/16/2001 AT 9:45:00
Bottle C0308,Q0108,8845,8858,P9132, Submitted 10/16/2001 AT
Collected By: TIGLAO/PATEL Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD25260
Method Test Description Results Units MDL Analyzed on Validator
Hexachlorobenzene < MDL ug/L 0.10 10/26/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/26/2001 DLV
Metolachlor <MDL ug/L 0.75 10/26/2001 DLV
Metribuzin < MDL ug/L 0.15 10/26/2001 DLV
Molinate <MDL ug/L 0.90 10/26/2001 DLV
Simazine <MDL ug/L 0.40 10/26/2001 DLV
Terbacil < MDL ug/L 2.0 10/26/2001 DLV
Recoveries for 4 of the 18 compounds in the MDL Standard were outside of their acceptance ranges. Recoveries
for 3 of the 18 compounds in the LCS Standard and the Spiked Sample were outside of their acceptance ranges.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/28/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/4/2001
Environmental Laboratories emailed Original 12/4/2001
NYS ELAP# 10108 Page 7 of 7