NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample BRONX
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 58
Dr. Ian Hurley ID of Source:
Received MC Collection 10/14/2001 AT 9:07:00
Bottle C0250,7473,6587,7868,9987,998 Submitted 10/14/2001 AT 9:55:00
Collected By: RIBANDO Sample Type: POT_DW
Comment: A scan of the extract prepared for the 508 PWS No.: Source Code:
analysis, from 35-550 amu using a ma
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD25045
Method Test Description Results Units MDL Analyzed on Validator
EPTC < MDL ug/L 1.0 10/25/2001 DLV
Hexachlorobenzene < MDL ug/L 0.10 10/25/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/25/2001 DLV
Metolachlor < MDL ug/L 0.75 10/25/2001 DLV
Metribuzin <MDL ug/L 0.15 10/25/2001 DLV
Molinate < MDL ug/L 0.90 10/25/2001 DLV
Simazine <MDL ug/L 0.40 10/25/2001 DLV
Terbacil <MDL ug/L 2.0 10/25/2001 DLV
The recovery for one of the Surrogate Standards in this sample was below its acceptance range. Recoveries for 3
of the 18 compounds in the MDL and LCS Standards were outside of their acceptance ranges. Recoveries for 4 of
the 18 compounds in the Spiked Sample were below their acceptance ranges.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/27/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/24/2001
Environmental Laboratories emailed Original 12/24/2001
NYS ELAP #10108 Page 7 of 7
NYC-WTC_000072265