REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: NYCDEP Bureau Water Sample NYC DEP
465 Columbus Ave. 19 WESTLAKE DRIVE
Valhalla, NY 10595 VALHALLA, N.Y.
Sample CROGH
Attention: Steve Schindler ID of Source:
Received LK Collection 10/28/2001 AT 7:40:00
Bottle C0443,Q302,301,303,P415,429,4 Submitted 10/29/2001 AT
Collected By: NEWMAN Sample Type: POT_DW
Comment: PWS No.: Source Code: 000
Type Descriptor:
Sample chilled on arrival? ; YES
Report
Sample No. AD26475
Method Test Description Results Units MDL Analyzed on Validator
bis(2-Ethylhexyl)phthalate <MDL ug/L 0.60 11/7/2001 DLV
Butachlor <MDL ug/L 0.40 11/7/2001 DLV
EPTC <MDL ug/L 1.0 11/7/2001 DLV
Hexachlorobenzene <MDL ug/L 0.10 11/7/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 11/7/2001 DLV
Metolachlor < MDL ug/L 0.75 11/7/2001 DLV
Metribuzin <MDL ug/L 0.15 11/7/2001 DLV
Molinate <MDL ug/L 0.90 11/7/2001 DLV
Simazine <MDL ug/L 0.40 11/7/2001 DLV
Terbacil < MDL ug/L 2.0 11/7/2001 DLV
The breakdown for Endrin in the Breakdown Standard was 39%. Recoveries for 4 of the 18 compounds in the MDL
Standard were outside of their acceptance ranges. Recoveries for 2 of the 18 compounds in the LCS Standard were
outside of their acceptance ranges. Recoveries for 3 of the 18 compounds in the Spiked Sample were outside of
their acceptance ranges.
GCMS Scan For Unknowns
Other unknown compounds ug/L 12/16/2001 DLV
A scan of the extract prepared from the 508 analysis, from 35 to 550 amu using a mass spectrometer, does not
reveal the presence of any non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/26/2001
Environmental Laboratories emailed Original 12/28/2001
NYS ELAP #10108 Page 6 of 6
NYC-WTC_000072045