REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample STATEN ISLAND
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 58250
Dr. Ian Hurley ID of Source:
Received EP Collection 10/25/2001 AT
Bottle c9792,p2005,2010,2117.q9800,9 Submitted 10/26/2001 AT
Collected By: TSUI Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : yes
Report
Sample No. AD26321
Method Test Description Results Units MDL Analyzed on Validator
Butachlor < MDL ug/L 0.40 11/6/2001 DLV
EPTC <MDL ug/L 1.0 11/6/2001 DLV
Hexachlorobenzene < MDL ug/L 0.10 11/6/2001 DLV
Hexachlorocyclopentadiene < MDL ug/L 0.10 11/6/2001 DLV
Metolachlor < MDL ug/L 0.75 11/6/2001 DLV
Metribuzin < MDL ug/L 0.15 11/6/2001 DLV
Molinate <MDL ug/L 0.90 11/6/2001 DLV
Simazine < MDL ug/L 0.40 11/6/2001 DLV
Terbacil <MDL ug/L 2.0 11/6/2001 DLV
The breakdown for Endrin in the Breakdown Standard was 56%. Recoveries for 4 of the 18 compounds in the MDL
Standard were outside of their acceptance ranges. Recoveries for 3 of the 18 compounds in the LCS Standard
were outside of their acceptance ranges. Recoveries for 3 of the 18 compounds in the Spiked Sample were outside
of their acceptance ranges. The level for bis(2-Ethylhexyl)phthalate was 0.88 ug/L in the Laboratory Blank.
GCMS Scan For Unknowns
Other unknown compounds ug/L 12/4/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/24/2001
Environmental Laboratories emailed Original 12/24/2001
NYS ELAP #10108 Page 7 of 7