NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample HILLVIEW
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 3
Dr. Ian Hurley ID of Source:
Rocoived EP Collection 10/5/2001 AT 10:00:00
Bottle k3675,3394,6801 ,p9714,9718,q9 Submitted 10/5/2001 AT 10:46:00
Collected By: PATEL/ODONISOK Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival?: yes
Report
Sample No. AD24395
Method Test Description Results Units MDL Analyzed on Validator
Benzo(a)pyrene <MDL ug/L 0.20 10/16/2001 DLV
bis(2-Ethylhexyl)adipate <MDL ug/L 0.60 10/16/2001 DLV
bis(2-Ethylhexyl)phthalate < MDL ug/L 0.60 10/16/2001 DLV
Butachlor <MDL ug/L 0.40 10/16/2001 DLV
EPTC < MDL ug/L 1.0 10/16/2001 DLV
Hexachlorobenzene <MDL ug/L 0.10 10/16/2001 DLV
Hexachlorocyclopentadiene < MDL ug/L 0.10 10/16/2001 DLV
Metolachlor < MDL ug/L 0.75 10/16/2001 DLV
Metribuzin <MDL ug/L 0.15 10/16/2001 DLV
Molinate < MDL ug/L 0.90 10/16/2001 DLV
Simazine <MDL ug/L 0.40 10/16/2001 DLV
Terbacil <MDL ug/L 2.0 10/16/2001 DLV
The recoveries for 4 of the 18 compounds in the MDL Standard and 2 of the 18 compounds in the LCS Standard
were outside of their acceptance ranges.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/7/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/20/2001
Environmental Laboratories emailed Original 12/20/2001
NYS ELAP # 10108 Page 7 of 7
NYC-WTC_000027370
OCR can misread numbers and units. Confirm readings against the page image before using them.