NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample STATEN ISLAND
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 52050
Dr. Ian Hurley ID of Source:
Received EP Collection 10/4/2001 AT 10:08:00
Bottle 9516,4312,4602,4521,9691,9689, Submitted 10/5/2001 AT 10:46:00
Collected By: DESSOURCES Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : yes
Report
Sample No. AD24401
Method Test Description Results Units MDL Analyzed on Validator
Benzo(a)pyrene < MDL ug/L 0.20 10/16/2001 DLV
bis(2-Ethyihexyl)adipate <MDL ug/L 0.60 10/16/2001 DLV
bis(2-Ethylhexyl)phthalate 0.88 ug/L 0.60 10/16/2001 DLV
Butachlor <MDL ug/L 0.40 10/16/2001 DLV
EPTC < MDL ug/L 1.0 10/16/2001 DLV
Hexachlorobenzene <MDL ug/L 0.10 10/16/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/16/2001 DLV
Metolachlor < MDL ug/L 0.75 10/16/2001 DLV
Metribuzin < MDL ug/L 0.15 10/16/2001 DLV
Molinate <MDL ug/L 0.90 10/16/2001 DLV
Simazine <MDL ug/L 0.40 10/16/2001 DLV
Terbacil <MDL ug/L 2.0 10/16/2001 DLV
The recovery for bis(2-Ethylhexyl)phthalate in the MDL Standard was above its acceptance range, probably due to
laboratory contamination.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/5/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35 - 550 amu using a mass spectrometer, does reveal the
presence of a hydrocarbon mixture, probably from an oil related substance. This substance could be in the sample
or could have been from a contaminated sample bottle. No other sample so far has been observed to contain a
similar substance. No other analysis performed has revealed a similar substance, thus there is no indication of
laboratory contamination at this time.
Approved Pam Dilsizian QA Officer Date Approved: 11/29/2001
Environmental Laboratories emailed Original 11/29/2001
NYS ELAP # 10108 Page 7 of 7