NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
gency: NYCDEP Bureau Water Sample NYC DEP
465 Columbus Ave. 19 WEST LAKE DRIVE
Valhalla, NY 10595 VALHALLA, N.Y.
Sample CRO GH
Attention: Steve Schindler ID of Source:
Received LK Collection 9/22/2001 AT 9:43:00
Bottle c0039,q8615,8626,8646,p8603,8 Submitted 9/24/2001 AT 9:29:00
Collected By: NEWMAN/ANTAL Sample Type: POT_DW
Comment: PWSNo.: Source Code: 000
Type Descriptor:
Sample chilled on arrival?: YES
Report
Sample No. AD23345
Method Test Description Results Units MDL Analyzed on Validator
Atrazine <MDL ug/L 0.10 10/4/2001 DLV
Benzo(a)pyrene <MDL ug/L 0.20 10/4/2001 DLV
bis(2-EthyIhexyI)adipate <MDL ug/L 0.60 10/4/2001 DLV
bis(2-EthyIhexyl)phthalate 1.1 ug/L 0.60 10/4/2001 DLV
Butachlor <MDL ug/L 0.40 10/4/2001 DLV
EPTC <MDL ug/L 1.0 10/4/2001 DLV
Hexachlorobenzene <MDL ug/L 0.10 10/4/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/4/2001 DLV
Metolachlor <MDL ug/L 0.75 10/4/2001 DLV
Metribuzin <MDL ug/L 0.15 10/4/2001 DLV
Molinate <MDL ug/L 0.90 10/4/2001 DLV
Simazine <MDL ug/L 0.07 10/4/2001 DLV
Terbacil <MDL ug/L 2.0 10/4/2001 DLV
Recoveries for three of the eighteen compounds in the MDL and LCS Standards were outside of their acceptance
ranges. The recovery for one of the three Surrogate Standards in this sample was above its acceptance range. The
level for bis(2-Ethylhexyl)phthalate in the Laboratory Blank was 2.2 ug/L.
GCMS Scan For Unknowns
Other unknown compounds ug/L 10/16/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35 - 550 amu using a mass spectrometer, reveals the
presence of non-target compounds. However, these compounds were observed in previous Laboratory Blanks,
though not in the Laboratory Blank associated with this sample.
Stat charge for VOLATILE organic Completed 9/25/2001 12:01 AM SV
Approved Donna Popp Chief of Env. Lab Services Date Approved: 10/22/2001
Environmental Laboratories Copy of Fax 10/22/2001
NYS ELAP # 10108 Page 7 of7
NYC-WTC_000026564